Enterprise Classic
A three-phase online UPS for whole facilities — hospitals, plants and critical infrastructure — IGBT-rectifier based, 80–500 kVA.
- Range
- 80–500 kVA
- Configuration
- Three-phase in / three-phase out (3:3)
- Topology
- Online double conversion · IGBT rectifier · DZnO-winding output isolation transformer · full DSP control

What it is
Enterprise Classic (80–500 kVA) is COMPACT's newer three-phase online double-conversion platform for enterprise business continuity — built to keep hospitals, continuous-process industries and critical infrastructure running through the volatile power and site conditions common in India.
An IGBT rectifier (input PF ≥ 0.99, THDi ≤ 3%), a DZnO-winding output isolation transformer, a 0.9 / unity output power factor, MTBF greater than 200,000 hours, a 5.7-inch LCD touch screen and optional N+X redundancy up to six units.
What it does
Three-phase online double conversion
Continuous regenerated 3:3 output — the load is isolated from raw-mains disturbances.
IGBT rectifier
Input power factor ≥ 0.99, THDi ≤ 3%.
DZnO-winding output isolation transformer
Output isolation for strong performance with unbalanced loads.
High MTBF
MTBF greater than 200,000 hours; MTTR under 0.5 hours.
5.7-inch LCD touch screen
Touch-screen interface with event history and large-capacity history storage.
Optional N+X redundancy
Optional N+X redundancy, parallel up to six units; ECO mode where the site permits it.
The engineering value
IGBT rectifier, DSP control
Full DSP control, a high input power factor (≥ 0.99) and a 0.9 / unity output power factor for more usable kW from the same footprint.
Built for Indian conditions
Re-specified by COMPACT — sourced from global manufacturing partners — to handle wide voltage swings, heat, dust and unreliable earthing.
Efficient at part load
Holds efficiency at lower loads, with an ECO mode where the site permits it.
Where it fits
Typical applications for this range — not an exhaustive list.
- Hospitals and critical-care environments
- Continuous-process industries and production lines
- Sensitive diagnostic and life-support medical equipment
- Industrial and commercial three-phase facility loads
- Any critical infrastructure requiring conditioned power and backup
Online double conversion with an IGBT rectifier
The IGBT rectifier feeds the DC bus and battery, the inverter continuously regenerates the three-phase output, and the output passes through a DZnO-winding output isolation transformer before it reaches the load. A static bypass handles overload and service.
Full DSP control governs the power path, with a 5.7-inch LCD touch screen for monitoring and event history, and optional N+X redundancy in parallel up to six units.
The rectifier and inverter run continuously, regenerating a clean output. The battery floats on the DC bus, held in reserve — current is always flowing to the load.
Model line-up
Real model designations and capacities transcribed from COMPACT's catalogue.
| Model | kVA | kW | Dimensions W×D×H (mm) | Net weight |
|---|---|---|---|---|
| EC-80 | 80 | 72 | 800 × 800 × 1800 | 580 kg |
| EC-100 | 100 | 90 | 800 × 800 × 1800 | 630 kg |
| EC-120 | 120 | 108 | 800 × 860 × 1700 | 680 kg |
| EC-160 | 160 | 144 | 1210 × 860 × 1950 | 790 kg |
| EC-200 | 200 | 180 | 1210 × 860 × 1950 | 1135 kg |
| EC-250 | 250 | 225 | 1210 × 860 × 1950 | 1275 kg |
| EC-300 | 300 | 270 | 1210 × 860 × 1950 | 1355 kg |
| EC-400 | 400 | 360 | 2380 × 860 × 1950 | 2090 kg |
| EC-500 | 500 | 450 | 2380 × 860 × 1950 | 2300 kg |
EC-80
- kVA
- 80
- kW
- 72
- Dimensions W×D×H (mm)
- 800 × 800 × 1800
- Net weight
- 580 kg
EC-100
- kVA
- 100
- kW
- 90
- Dimensions W×D×H (mm)
- 800 × 800 × 1800
- Net weight
- 630 kg
EC-120
- kVA
- 120
- kW
- 108
- Dimensions W×D×H (mm)
- 800 × 860 × 1700
- Net weight
- 680 kg
EC-160
- kVA
- 160
- kW
- 144
- Dimensions W×D×H (mm)
- 1210 × 860 × 1950
- Net weight
- 790 kg
EC-200
- kVA
- 200
- kW
- 180
- Dimensions W×D×H (mm)
- 1210 × 860 × 1950
- Net weight
- 1135 kg
EC-250
- kVA
- 250
- kW
- 225
- Dimensions W×D×H (mm)
- 1210 × 860 × 1950
- Net weight
- 1275 kg
EC-300
- kVA
- 300
- kW
- 270
- Dimensions W×D×H (mm)
- 1210 × 860 × 1950
- Net weight
- 1355 kg
EC-400
- kVA
- 400
- kW
- 360
- Dimensions W×D×H (mm)
- 2380 × 860 × 1950
- Net weight
- 2090 kg
EC-500
- kVA
- 500
- kW
- 450
- Dimensions W×D×H (mm)
- 2380 × 860 × 1950
- Net weight
- 2300 kg
Nine capacity points in the 80–500 kVA sub-range.
Technical specification
Transcribed from COMPACT's product catalogue.
| Input | |
|---|---|
| Wiring | Three-phase five-wire (3Φ + N + PE) |
| Rated voltage | 380 / 400 / 415 VAC |
| Voltage range | 346–456 V (full load); 304–346 V (10% derating) |
| Rated frequency | 50–60 Hz (± 5 Hz) |
| Power factor | ≥ 0.99 |
| THDi | ≤ 3% |
| Rectifier delayed start | 10 s (1–300 s, settable) |
| Bypass voltage range | ± 20% (settable) |
| Output | |
| Wiring | Three-phase five-wire (3Φ + N + PE) |
| Rated voltage | 380 / 400 / 415 VAC |
| Voltage regulation | ± 1% |
| Frequency regulation | 50–60 Hz ± 0.1% in battery mode |
| Waveform | Sinusoidal |
| Power factor | 0.9 / unity |
| Voltage distortion (THDv) | ≤ 2% linear load, ≤ 5% non-linear load |
| Crest factor | 3 : 1 |
| Overload | 105–110% for 60 min, 110–125% for 10 min |
| Battery & system | |
| DC voltage | 600 Vdc (supports 576 / 588 / 612 / 624 Vdc) |
| Number of batteries | 12 V × 50 pcs (supports 48 / 49 / 51 / 52 pcs) |
| Efficiency | Line mode ≥ 94% (all models); ECO mode ≥ 97% (EC-80–EC-300), ≥ 98% (EC-400–EC-500) |
| Max parallel connections | 6 units |
| Protections | Short circuit, overload, over-temperature, over/under-voltage, battery low voltage, fan failure |
| Communications | Standard: RS232, RS485, dry contacts. Optional: SNMP card, temperature compensation, SMS alarms |
| Display | 5.7" LCD touch screen |
| Environmental | |
| Operating temperature | 0 °C – 40 °C |
| Storage temperature | -25 °C – 55 °C (without battery) |
| Relative humidity | 0% – 95% (non-condensing) |
| Altitude | ≤ 1000 m; derate 1% per additional 100 m |
| IP rating | IP20 |
| Noise level at 1 m | < 65 dB (EC-80–EC-300) / < 70 dB (EC-400–EC-500) |
Input
- Wiring
- Three-phase five-wire (3Φ + N + PE)
- Rated voltage
- 380 / 400 / 415 VAC
- Voltage range
- 346–456 V (full load); 304–346 V (10% derating)
- Rated frequency
- 50–60 Hz (± 5 Hz)
- Power factor
- ≥ 0.99
- THDi
- ≤ 3%
- Rectifier delayed start
- 10 s (1–300 s, settable)
- Bypass voltage range
- ± 20% (settable)
Output
- Wiring
- Three-phase five-wire (3Φ + N + PE)
- Rated voltage
- 380 / 400 / 415 VAC
- Voltage regulation
- ± 1%
- Frequency regulation
- 50–60 Hz ± 0.1% in battery mode
- Waveform
- Sinusoidal
- Power factor
- 0.9 / unity
- Voltage distortion (THDv)
- ≤ 2% linear load, ≤ 5% non-linear load
- Crest factor
- 3 : 1
- Overload
- 105–110% for 60 min, 110–125% for 10 min
Battery & system
- DC voltage
- 600 Vdc (supports 576 / 588 / 612 / 624 Vdc)
- Number of batteries
- 12 V × 50 pcs (supports 48 / 49 / 51 / 52 pcs)
- Efficiency
- Line mode ≥ 94% (all models); ECO mode ≥ 97% (EC-80–EC-300), ≥ 98% (EC-400–EC-500)
- Max parallel connections
- 6 units
- Protections
- Short circuit, overload, over-temperature, over/under-voltage, battery low voltage, fan failure
- Communications
- Standard: RS232, RS485, dry contacts. Optional: SNMP card, temperature compensation, SMS alarms
- Display
- 5.7" LCD touch screen
Environmental
- Operating temperature
- 0 °C – 40 °C
- Storage temperature
- -25 °C – 55 °C (without battery)
- Relative humidity
- 0% – 95% (non-condensing)
- Altitude
- ≤ 1000 m; derate 1% per additional 100 m
- IP rating
- IP20
- Noise level at 1 m
- < 65 dB (EC-80–EC-300) / < 70 dB (EC-400–EC-500)
Consider alongside
20–300 kVAEnterprise Classic
Three-phase online double-conversion UPS, transformer-based with output galvanic isolation — 20–300 kVA.
10–80 kVAEnterprise YD Series
Vertical-modular, DSP-controlled three-phase online UPS engineered for data-centre-grade RAS.
Up to 300 kVAPrecision Power Conditioner (PPC)
Solid-state precision voltage conditioning — no moving parts, correction in under 20 milliseconds.

Batteries
SMF, tubular and lithium-ion battery banks, sized and maintained to your backup requirement.
Talk to us to uncover the hidden problems
Tell us the load, the site and the supply. COMPACT's pre-sales team will confirm whether Enterprise Classic 500 is the right fit — and flag anything else the site needs that a spec sheet alone would miss.