Precision Power Conditioner Specification
Technical Specifications
Single phase Precision PWM Line Conditioners Three phase Precision PWM Line Conditioners
Feature ± 20% Full Regulation ± 20% Full Regulation
Electrical
Capacity in KVA (KW) 1 KVA TO 15 KVA 3 KVA TO 100 KVA
Regulator Engine High Frequency 20 Khz IGBT driven voltage regulation convertor
Input
* Nominal Voltage 230 Volts AC ,Single Phase 400 Volts AC ,Three Phase
*Nominal Voltage (typical output regulation within +/-1% of nominal) 184-276 volts AC 170-290 volts AC
Sag Voltage % for which output would stay within 20 % of nominal voltage (as per ITIC Curve for Electronic devices) 35 % 40 %
Swell Voltage % for which output would stay within 10 % of nominal voltage (as per ITIC Curve for Electronic devices) 30 %
Nominal frequency 47- 63 Hz
Output
*Nominal Voltage 230 Volts AC ,Single phase Hz 400 Volts AC ,Three phase
Power efficiency (with 20-100 % load conditions & worst incoming voltage ) Over 96 %
Voltage regulation (typical excluding meter error ) + / -1 %
Physical
Dimensions (mm) 435D * 300 W * 175H upto 5 KVA 460D * 360 W * 980H upto 5 KVA
540D * 405 W * 280H upto 15 KVA 660D * 660 W * 570H upto 40 KVA
660D * 660 W * 725H upto 50 KVA
813D * 813 W * 838H upto 100 KVA
Weight (approx ) 16 kgs for smallest capacity to 60 kgs for largest capacity 65 kgs for smallest capacity to 350 kgs for largest capacity
Annunciation LED display for Regulation mode ,Byepass mode & Fault conditioners
Environment
Ambient temperature 0 ° to + 45° centigrade (32 ° to 113° farhenheit) 10 to 90 % RH non -condensing
Cooling method Natural Cooled Fan Cooled
Standards & Safety Designed to meet UL 60950 -1 Standards ,Protection Class IP 20
Overload & Short Circuit Protection Through suitably rated input circuit breaker
Protective features
Soft Switch - On This feature ensure that the output voltage is never high than the input voltage upon switch - on before it commences full stabilization
Automatic Byepass Regulator engine will be automatically byepassed when there is a fault condition
Surge Test Conditions per class 2 Surge (combination wave )
Surge let throgh voltages 1.2 * 50 µs 6 kV, 8 * 20µs ,3 kA waveform, L- N < 300V
Warranty Two Year limited Warranty ,covering repair / replacement of defective parts
 
Copyright © 2012 Compactups, Developed by Computer Ware (India) Pvt.Ltd.